Pool Dehumidifier
The Pool Dehumidifier is designed for areas such as indoor pools and specialized dehumidification processes. Manufactured from 50 mm thick aluminum profiles, this unit features a panel structure filled with 50 mm rock wool insulation and can be produced with a flow rate range of 0-25,000 m³/h. The batteries are epoxy-coated for corrosion resistance. Plug fans are used as standard, while EC fans can also be used as an option. Thermostatic expansion valves are used as standard, while electronic expansion valves can also be used upon request.
The MCC and DDC panel, compliant with EN60204/1, is included on the device and is shipped with the necessary power and control cable installations. If there is no suitable plumbing for a water-based heating system, an electric heater production option is also available. The automatic control system, which offers operation for seasonal transitions, summer nights, and winter days, increases the device's efficiency and ease of use.
General Features
- X Applications: Indoor Pools, Special Dehumidification Processes, etc.
- X The pool dehumidifier is manufactured from 50 mm aluminum profile.
- X It has a panel structure filled with 50 mm rock wool.
- X Production can be carried out in a flow rate range of 000 – 25,000 m³/h.
- X The batteries are epoxy-coated for corrosion resistance.
- X Plug fan production is possible. Optional EC fan production is possible.
- X A thermostatic expansion valve is used. An optional electronic expansion valve can be used.
- X EN60204/1 compliant MCC and DDC panel devices are included and shipped with the necessary power and control cable installations already in place.
- X If there is no plumbing suitable for a water-based heating system, production can be carried out using electric heaters.
- X An automatic control system is available that allows operation in summer night and winter day positions during seasonal transitions.
Device Models
Plate Heat Exchanger Pool Dehumidifier
Heat Pipe Pool Dehumidifier
Mixture Air Pool Dehumidifier
Capacity Value
| ||||||
Flow Rate (m³/h) | Out of Device Pressure (Pa) | Moisture Removal Capacity (kg/h) | Cooling Battery Capacity (kW) | Heating Battery Capacity (kW) | Wet Battery Capacity 80°C/60°C (kW) | Total Power Consumed (kW) |
3000 | 450 | 19,1 | 16,46 | 20,70 | 27,50 | 5,3 |
4500 | 450 | 28,6 | 25,37 | 31,40 | 43,80 | 8,5 |
6000 | 450 | 38,2 | 33,30 | 40,10 | 56,00 | 10,0 |
8000 | 450 | 50,9 | 42,11 | 51,50 | 76,70 | 13,8 |
10000 | 450 | 63,7 | 52,00 | 61,90 | 96,00 | 18,3 |
12000 | 450 | 76,3 | 63,20 | 79,30 | 120,20 | 27,7 |
16000 | 450 | 101,8 | 81,80 | 100,00 | 162,80 | 32,7 |
18000 | 450 | 114,5 | 96,66 | 121,70 | 175,30 | 40,8 |
20000 | 450 | 127,2 | 100,93 | 123,80 | 200,20 | 39,3 |
25000 | 450 | 159,0 | 128,63 | 158,50 | 247,90 | 44,5 |
| ||||||
Flow Rate (m³/h) | Out of Device Pressure (Pa) | Moisture Removal Capacity (kg/h) | Cooling Battery Capacity (kW) | Heating Battery Capacity (kW) | Wet Battery Capacity 80°C/60°C (kW) | Total Power Consumed (kW) |
3000 | 450 | 19,1 | 20,10 | 25,90 | 27,60 | 5,6 |
4500 | 450 | 28,6 | 30,50 | 36,60 | 43,60 | 9,4 |
6000 | 450 | 38,2 | 38,00 | 45,80 | 57,00 | 12,9 |
8000 | 450 | 50,9 | 49,00 | 59,70 | 77,90 | 16,0 |
10000 | 450 | 63,7 | 65,10 | 80,10 | 93,40 | 20,2 |
12000 | 450 | 76,3 | 80,30 | 99,70 | 116,60 | 23,9 |
16000 | 450 | 101,8 | 102,00 | 126,00 | 158,90 | 30,3 |
18000 | 450 | 114,5 | 124,20 | 157,40 | 175,30 | 39,9 |
20000 | 450 | 127,2 | 133,20 | 165,00 | 200,20 | 41,1 |
25000 | 450 | 159,0 | 164,00 | 204,00 | 249,20 | 55,1 |